Auto-Light Interfaces and Connection Examples

Version 5.2 von jadomatis am 2026/09/08 08:29

Description: Learn how to identify the Auto-Light X0 mains connection, X1 safety and production interface, and X2 axis interface. The pin assignments and diagrams are reproduced from the supplied operating manual in English.

Qualified integration work only: The manual diagrams are connection examples, not a complete safety design or permission to wire an energised system. An appropriately qualified integrator must design, calculate, isolate, wire, validate, and document the complete safety-related control system for the delivered machine.


Connection Locations

X0 mains power, X1 safety and production I/O, and X2 axis control are located at the rear of the laser rack. USB, Ethernet, and HDMI connections support the delivered workstation, network, and display arrangement.

1788847354911-289.png
 

X0 Mains Supply

The manual identifies X0 as a 230 V / 600 W mains-supply interface including the main switch. Before connection, verify the actual nameplate, protective conductor, supply frequency, protective measures, disconnecting means, cable, plug, and site electrical documentation.

Keep X0 separate from model consumption data: The X0 declaration is the documented supply-interface value. The lower power-consumption figures listed for individual laser-source variants in Technical Specifications do not replace the delivered supply and protection requirements.

X1 Laser Interface - Pin Assignment

Pin(s)SignalManual description / use
1-2Emergency-stop circuit 1External wiring through a safety module required
3-4Emergency-stop circuit 2External wiring through a safety module required
5-6Emergency-stop acknowledgementAcknowledgement contact
7-8Shutter circuit 1External wiring through a safety module required
9-10Shutter circuit 2External wiring through a safety module required
11-12Shutter acknowledgementAcknowledgement contact
13+24 VSupply voltage for inputs
14External START24 V input
15External STOP24 V input
16Emergency-stop status24 V output
17SHUTTER status24 V output
18LASER READY status24 V output
19LASER BUSY status24 V output
20LASER END status24 V output
21-22Inputs 4 and 524 V inputs
23-24Outputs 4 and 524 V outputs
25GNDGround for outputs

X1 Emergency-Stop Connection Examples

The manual example routes two external emergency-stop channels through a safety module. Circuit 1 uses X1.1/X1.2 and circuit 2 uses X1.3/X1.4. Both channels belong to the integrated safety system and must be assessed and validated as part of the host machine.

1788848413333-368.png

Example: dual emergency-stop circuits at X1.1-X1.4.

Emergency-stop acknowledgement is provided at X1.5/X1.6. TAcknowledgement is required at every restart of the system and after every operation of the emergency stop.

1788848413336-918.png

Example: emergency-stop acknowledgement at X1.5/X1.6.