... ... @@ -105,5 +105,38 @@
105 105  
106 106  [[**Example: shutter acknowledgement at X1.11/X1.12.**>>image:1788776541211-163.png]]
107 107  
108 +(% class="box warningmessage" %)
109 +(((
110 +**Diagnostic meaning: **If either emergency-stop or shutter channel is open, inconsistent, or not acknowledged, LASER READY may remain absent. Never bridge a channel to prove this diagnosis; use the host safety-module indications and approved electrical test procedure.
111 +)))
108 108  
109 -
113 +
114 += X1 Production and Status I/O =
115 +
116 +After the safety circuits are valid, use the documented X1 command and status sequence to localise a control fault. Record which state is missing or which output changes first.
117 +
118 +|**Pin group**|**Documented function**|**Diagnostic use**
119 +|X1.13-X1.15|+24 V input supply; External START; External STOP|If START has no effect, confirm LASER READY before checking the host command. An active STOP or missing start condition can stop a cycle.
120 +|X1.16-X1.17|Emergency-stop status; SHUTTER status|These show whether the safety chain and shutter permission have reached the expected state.
121 +|X1.18-X1.20|LASER READY; LASER BUSY; LASER END|Use the transition order to distinguish a missing ready condition, a cycle that never started, or a cycle that did not complete normally.
122 +|X1.21-X1.24|Inputs 4 and 5; Outputs 4 and 5|Their assigned use depends on the delivered integration. Check the approved electrical documentation before interpreting them.
123 +|X1.25|GND for outputs|Active outputs supply 24 V and are evaluated against this output ground. The documented maximum output current is 250 mA.
124 +
125 +
126 +
127 +== Expected Diagnostic Sequence ==
128 +
129 +1. Verify both emergency-stop channels and the required acknowledgement.
130 +1. Verify both shutter channels, the guard condition, and shutter acknowledgement.
131 +1. Confirm Emergency-stop status and SHUTTER status before expecting LASER READY.
132 +1. With LASER READY present, check whether External START is received and whether LASER BUSY then LASER END follows the validated host sequence.
133 +1. If the sequence differs, record the states and stop. Do not change timing, wiring, or safety logic unless authorised for the integration.
134 +
135 +(% class="box warningmessage" %)
136 +(((
137 +**Status outputs are evidence, not permission to bypass: **A missing signal helps locate the fault but does not authorise forcing an input or output. Troubleshoot the host safety system, Auto-Light interface, and controller as the validated integrated machine.
138 +)))
139 +
140 += X2 Axis Interface =
141 +
142 +X2 is the 25-pin Sub-D axis interface. The manual groups direction and step outputs for X, Y, Z, and R with zero/reference signals. Use this pinout to identify the affected axis and whether the symptom concerns commanded motion or the reference input; do not use it as an energised probing guide.