... ... @@ -83,4 +83,17 @@ 83 83 (% style="font-size:14px" %) (%%)The X1 emergency-stop connection uses two external safety channels. Circuit 1 is connected through X1.1/X1.2 and circuit 2 through X1.3/X1.4. The external safety module must validate both channels; a discrepancy belongs to the integrated safety chain, not to normal AnyMarker job handling. 84 84 \\ 85 85 86 -[[Example: dual emergency-stop safety circuits at X1.1-X1.4.>>image:1788775595167-399.png]] 86 +[[**Example: dual emergency-stop safety circuits at X1.1-X1.4.**>>image:1788775595167-399.png]] 87 + 88 + 89 +Emergency-stop acknowledgement is provided at X1.5/X1.6. At every system restart and after every emergency-stop actuation acknowledgement is required. If acknowledgement is not accepted, do not repeat the reset indefinitely; record the host safety state and escalate a recurring condition. 90 +\\ 91 + 92 +[[**Example: emergency-stop acknowledgement at X1.5/X1.6.**>>image:1788775764610-963.png]] 93 + 94 + 95 += X1 Safety Interface - Shutter Circuit = 96 + 97 +The shutter connection also uses two external safety channels: circuit 1 at X1.7/X1.8 and circuit 2 at X1.9/X1.10. Opening the protective enclosure must interrupt the shutter circuit. A closed and validated shutter circuit permits active mode; it does not by itself command a marking cycle. 98 + 99 +