Changes for page Troubleshooting
Last modified by jadomatis on 2026/09/07 13:51
Summary
-
Page properties (1 modified, 0 added, 0 removed)
Details
- Page properties
-
- Content
-
... ... @@ -80,14 +80,5 @@ 80 80 **Qualified personnel only: **The following signal map helps identify where a fault belongs. Electrical measurement, connector removal, rewiring, safety-module work, and axis-service work require the system to be isolated and may be performed only by personnel authorised for the delivered integration. 81 81 ))) 82 82 83 -[[image:1788773598823-721.png]] 84 84 85 - 86 -|**Interface**|**Relevant signals**|**Diagnostic meaning** 87 -|X1 safety|Pins 1-4: dual emergency-stop circuits; 5-6: acknowledgement|Both channels and the approved acknowledgement must be valid before operation. 88 -|X1 shutter|Pins 7-10: dual shutter circuits; 11-12: acknowledgement|Opening the protective enclosure must interrupt the shutter circuit. Never bypass either channel. 89 -|X1 control|13: +24 V; 14: START; 15: STOP|Check the host command sequence only after the safety states are valid. 90 -|X1 status|16: E-stop; 17: SHUTTER; 18: READY; 19: BUSY; 20: END|Record which output is absent or changes first. Active outputs provide 24 V; maximum output current is 250 mA. 91 -|X2 axes|Direction/step for X, Y, Z, R; zero inputs|A motion or reference fault may belong to the host mechanics, axis wiring, limit/reference input, or configuration. 92 - 93 - 84 +[[image:1788773598823-721.png]]