Changes for page Troubleshooting

Last modified by jadomatis on 2026/09/07 13:51

From version 2.2
edited by jadomatis
on 2026/09/07 11:40
Change comment: There is no comment for this version
To version 6.13
edited by jadomatis
on 2026/09/07 12:54
Change comment: There is no comment for this version

Summary

Details

Page properties
Content
... ... @@ -73,12 +73,102 @@
73 73  For software messages, device connection, and job handling, use the **[[AnyMarker Designer XWiki>>url:https://docs2.anymarker.de]]**.
74 74  
75 75  
76 -= X1 and X2 Diagnostic Boundary =
76 += X1 Safety Interface - Emergency-Stop Circuit =
77 77  
78 78  (% class="box errormessage" %)
79 79  (((
80 -**Qualified personnel only: **The following signal map helps identify where a fault belongs. Electrical measurement, connector removal, rewiring, safety-module work, and axis-service work require the system to be isolated and may be performed only by personnel authorised for the delivered integration.
80 +**Qualified personnel only: **The diagrams identify the documented interface connections; they are not instructions to probe or rewire an energized system. Electrical measurement, connector removal, rewiring, safety-module work, and axis-service work require isolation and personnel authorized for the delivered integration.
81 81  )))
82 82  
83 +(% style="font-size:14px" %) (%%)The X1 emergency-stop connection uses two external safety channels. Circuit 1 is connected through X1.1/X1.2 and circuit 2 through X1.3/X1.4. The external safety module must validate both channels; a discrepancy belongs to the integrated safety chain, not to normal AnyMarker job handling.
84 +\\
83 83  
84 -[[image:1788773598823-721.png]]
86 +[[**Example: dual emergency-stop safety circuits at X1.1-X1.4.**>>image:1788775595167-399.png]]
87 +
88 +
89 +Emergency-stop acknowledgement is provided at X1.5/X1.6. At every system restart  and after every emergency-stop actuation acknowledgement is required. If acknowledgement is not accepted, do not repeat the reset indefinitely; record the host safety state and escalate a recurring condition.
90 +\\
91 +
92 +[[**Example: emergency-stop acknowledgement at X1.5/X1.6.**>>image:1788775764610-963.png]]
93 +
94 +
95 += X1 Safety Interface - Shutter Circuit =
96 +
97 +The shutter connection also uses two external safety channels: circuit 1 at X1.7/X1.8 and circuit 2 at X1.9/X1.10. Opening the protective enclosure must interrupt the shutter circuit. A closed and validated shutter circuit permits active mode; it does not by itself command a marking cycle.
98 +
99 +
100 +[[**Example: dual shutter safety circuits at X1.7-X1.10.**>>image:1788776328447-524.png]]
101 +
102 +
103 +Shutter acknowledgement is provided at X1.11/X1.12. When SHUTTER status is missing, first verify the host guard and safety-module indications. A pin-level test or change to the acknowledgement circuit is an integration-service task.
104 +\\
105 +
106 +[[**Example: shutter acknowledgement at X1.11/X1.12.**>>image:1788776541211-163.png]]
107 +
108 +(% class="box warningmessage" %)
109 +(((
110 +**Diagnostic meaning: **If either emergency-stop or shutter channel is open, inconsistent, or not acknowledged, LASER READY may remain absent. Never bridge a channel to prove this diagnosis; use the host safety-module indications and approved electrical test procedure.
111 +)))
112 +
113 +
114 += X1 Production and Status I/O =
115 +
116 +After the safety circuits are valid, use the documented X1 command and status sequence to localise a control fault. Record which state is missing or which output changes first.
117 +
118 +|**Pin group**|**Documented function**|**Diagnostic use**
119 +|X1.13-X1.15|+24 V input supply; External START; External STOP|If START has no effect, confirm LASER READY before checking the host command. An active STOP or missing start condition can stop a cycle.
120 +|X1.16-X1.17|Emergency-stop status; SHUTTER status|These show whether the safety chain and shutter permission have reached the expected state.
121 +|X1.18-X1.20|LASER READY; LASER BUSY; LASER END|Use the transition order to distinguish a missing ready condition, a cycle that never started, or a cycle that did not complete normally.
122 +|X1.21-X1.24|Inputs 4 and 5; Outputs 4 and 5|Their assigned use depends on the delivered integration. Check the approved electrical documentation before interpreting them.
123 +|X1.25|GND for outputs|Active outputs supply 24 V and are evaluated against this output ground. The documented maximum output current is 250 mA.
124 +
125 +
126 +
127 +== Expected Diagnostic Sequence ==
128 +
129 +1. Verify both emergency-stop channels and the required acknowledgement.
130 +1. Verify both shutter channels, the guard condition, and shutter acknowledgement.
131 +1. Confirm Emergency-stop status and SHUTTER status before expecting LASER READY.
132 +1. With LASER READY present, check whether External START is received and whether LASER BUSY then LASER END follows the validated host sequence.
133 +1. If the sequence differs, record the states and stop. Do not change timing, wiring, or safety logic unless authorised for the integration.
134 +
135 +(% class="box warningmessage" %)
136 +(((
137 +**Status outputs are evidence, not permission to bypass: **A missing signal helps locate the fault but does not authorise forcing an input or output. Troubleshoot the host safety system, Auto-Light interface, and controller as the validated integrated machine.
138 +)))
139 +
140 +
141 +
142 += X2 Axis Interface =
143 +
144 +X2 is the 25-pin Sub-D axis interface. Direction and step outputs for X, Y, Z, and R are grouped with zero/reference signals. Use this pinout to identify the affected axis and whether the symptom concerns commanded motion or the reference input; do not use it as an energized probing guide.
145 +
146 +(% class="table-condensed table-striped" style="width:604px" %)
147 +|=(% style="width: 92px;" %)Pin|=(% style="width: 160px;" %)Direction|=(% style="width: 350px;" %)Description
148 +|(% style="width:92px" %)1|(% style="width:160px" %)Output|(% style="width:350px" %)Direction X
149 +|(% style="width:92px" %)2|(% style="width:160px" %)Output|(% style="width:350px" %)Step X
150 +|(% style="width:92px" %)3|(% style="width:160px" %)Output|(% style="width:350px" %)Direction Y
151 +|(% style="width:92px" %)4|(% style="width:160px" %)Output|(% style="width:350px" %)Step Y
152 +|(% style="width:92px" %)5|(% style="width:160px" %)Output|(% style="width:350px" %)Direction Z
153 +|(% style="width:92px" %)6|(% style="width:160px" %)Output|(% style="width:350px" %)Step Z
154 +|(% style="width:92px" %)7|(% style="width:160px" %)Output|(% style="width:350px" %)Direction R
155 +|(% style="width:92px" %)8|(% style="width:160px" %)Output|(% style="width:350px" %)Step R
156 +|(% style="width:92px" %)9|(% style="width:160px" %)Output|(% style="width:350px" %)Zero X
157 +|(% style="width:92px" %)10|(% style="width:160px" %)-|(% style="width:350px" %)Not connected
158 +|(% style="width:92px" %)11|(% style="width:160px" %)Input|(% style="width:350px" %)Zero Y
159 +|(% style="width:92px" %)12|(% style="width:160px" %)-|(% style="width:350px" %)Not connected
160 +|(% style="width:92px" %)13|(% style="width:160px" %)Input|(% style="width:350px" %)Zero Z
161 +|(% style="width:92px" %)14|(% style="width:160px" %)-|(% style="width:350px" %)Not connected
162 +|(% style="width:92px" %)15|(% style="width:160px" %)Input|(% style="width:350px" %)Zero R
163 +|(% style="width:92px" %)16|(% style="width:160px" %)-|(% style="width:350px" %)Not connected
164 +|(% style="width:92px" %)17|(% style="width:160px" %)Output|(% style="width:350px" %)GND
165 +|(% style="width:92px" %)18|(% style="width:160px" %)-|(% style="width:350px" %)Not connected
166 +|(% style="width:92px" %)19|(% style="width:160px" %)Output|(% style="width:350px" %)+5V supply
167 +|(% style="width:92px" %)20|(% style="width:160px" %)-|(% style="width:350px" %)Not connected
168 +|(% style="width:92px" %)21|(% style="width:160px" %)-|(% style="width:350px" %)Not connected
169 +|(% style="width:92px" %)22|(% style="width:160px" %)-|(% style="width:350px" %)Not connected
170 +|(% style="width:92px" %)23|(% style="width:160px" %)-|(% style="width:350px" %)Not connected
171 +|(% style="width:92px" %)24|(% style="width:160px" %)-|(% style="width:350px" %)Not connected
172 +|(% style="width:92px" %)25|(% style="width:160px" %)-|(% style="width:350px" %)Not connected
173 +
174 +
1788775595167-399.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.jadomatis
Size
... ... @@ -1,0 +1,1 @@
1 +45.5 KB
Content
1788775764610-963.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.jadomatis
Size
... ... @@ -1,0 +1,1 @@
1 +15.3 KB
Content
1788776328447-524.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.jadomatis
Size
... ... @@ -1,0 +1,1 @@
1 +45.6 KB
Content
1788776541211-163.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.jadomatis
Size
... ... @@ -1,0 +1,1 @@
1 +14.8 KB
Content