80 80  **Qualified personnel only: **The following signal map helps identify where a fault belongs. Electrical measurement, connector removal, rewiring, safety-module work, and axis-service work require the system to be isolated and may be performed only by personnel authorised for the delivered integration.
81 81  )))
82 82  
83 +[[image:1788773598823-721.png]]
83 83  
84 -[[image:1788773598823-721.png]]
85 +
86 +|**Interface**|**Relevant signals**|**Diagnostic meaning**
87 +|X1 safety|Pins 1-4: dual emergency-stop circuits; 5-6: acknowledgement|Both channels and the approved acknowledgement must be valid before operation.
88 +|X1 shutter|Pins 7-10: dual shutter circuits; 11-12: acknowledgement|Opening the protective enclosure must interrupt the shutter circuit. Never bypass either channel.
89 +|X1 control|13: +24 V; 14: START; 15: STOP|Check the host command sequence only after the safety states are valid.
90 +|X1 status|16: E-stop; 17: SHUTTER; 18: READY; 19: BUSY; 20: END|Record which output is absent or changes first. Active outputs provide 24 V; maximum output current is 250 mA.
91 +|X2 axes|Direction/step for X, Y, Z, R; zero inputs|A motion or reference fault may belong to the host mechanics, axis wiring, limit/reference input, or configuration.