jadomatis 2.2 1 **Description**: Learn how to identify the Auto-Light X0 mains connection, X1 safety and production interface, and X2 axis interface. The pin assignments and diagrams are reproduced from the supplied operating manual in English.
2
3 (% class="box errormessage" %)
4 (((
5 **Qualified integration work only: **The manual diagrams are connection examples, not a complete safety design or permission to wire an energised system. An appropriately qualified integrator must design, calculate, isolate, wire, validate, and document the complete safety-related control system for the delivered machine.
6 )))
7
8 ----
9
jadomatis 5.3 10
jadomatis 2.2 11 = Connection Locations =
12
13 X0 mains power, X1 safety and production I/O, and X2 axis control are located at the rear of the laser rack. USB, Ethernet, and HDMI connections support the delivered workstation, network, and display arrangement.
14
jadomatis 20.2 15 [[**Auto-Light front and rear rack panels. X1 and X2 are located on the rear panel.**>>image:1788848686104-199.png]]
jadomatis 2.2 16
jadomatis 19.2 17
18 = X0 Mains Supply =
19
jadomatis 20.2 20 X0 is a 230 V / 600 W mains-supply interface including the main switch. Before connection, verify the actual nameplate, protective conductor, supply frequency, protective measures, disconnecting means, cable, plug, and site electrical documentation.
jadomatis 19.2 21
jadomatis 20.5 22 (% class="box warningmessage" %)
23 (((
jadomatis 19.2 24 **Keep X0 separate from model consumption data: **The X0 declaration is the documented supply-interface value. The lower power-consumption figures listed for individual laser-source variants in Technical Specifications do not replace the delivered supply and protection requirements.
jadomatis 20.5 25 )))
jadomatis 19.2 26
jadomatis 20.2 27
jadomatis 19.2 28 = X1 Laser Interface - Pin Assignment =
29
jadomatis 20.2 30 (% class="table-condensed table-striped" %)
jadomatis 19.2 31 |**Pin(s)**|**Signal**|**Manual description / use**
32 |1-2|Emergency-stop circuit 1|External wiring through a safety module required
33 |3-4|Emergency-stop circuit 2|External wiring through a safety module required
34 |5-6|Emergency-stop acknowledgement|Acknowledgement contact
35 |7-8|Shutter circuit 1|External wiring through a safety module required
36 |9-10|Shutter circuit 2|External wiring through a safety module required
37 |11-12|Shutter acknowledgement|Acknowledgement contact
38 |13|+24 V|Supply voltage for inputs
39 |14|External START|24 V input
40 |15|External STOP|24 V input
41 |16|Emergency-stop status|24 V output
42 |17|SHUTTER status|24 V output
43 |18|LASER READY status|24 V output
44 |19|LASER BUSY status|24 V output
45 |20|LASER END status|24 V output
46 |21-22|Inputs 4 and 5|24 V inputs
47 |23-24|Outputs 4 and 5|24 V outputs
48 |25|GND|Ground for outputs
49
50
51
52 = X1 Emergency-Stop Connection Examples =
53
jadomatis 20.3 54 Circuit 1 uses X1.1/X1.2 and circuit 2 uses X1.3/X1.4. Both channels belong to the integrated safety system and must be assessed and validated as part of the host machine.
jadomatis 19.2 55
jadomatis 20.5 56 [[**Example: dual emergency-stop circuits at X1.1-X1.4.**>>image:1788848686108-737.png]]
jadomatis 19.2 57
58
59 Emergency-stop acknowledgement is provided at X1.5/X1.6. The source manual states that acknowledgement is required at every restart of the system and after every operation of the emergency stop.
60
jadomatis 20.5 61 [[**Example: emergency-stop acknowledgement at X1.5/X1.6.**>>image:1788848686109-592.png]]
jadomatis 19.2 62
jadomatis 20.6 63 (% class="box warningmessage" %)
64 (((
jadomatis 19.2 65 **Reset is not a safety function: **Acknowledgement may be accepted only after the cause of the stop has been removed, the hazard area is clear, and the host safety system permits reset. It must not initiate hazardous movement or laser emission by itself.
jadomatis 20.6 66 )))
jadomatis 19.2 67
68
69 = X1 Shutter Connection Examples =
70
71 The shutter interface also uses two external channels. Circuit 1 uses X1.7/X1.8 and circuit 2 uses X1.9/X1.10. The manual requires the shutter circuit to be interrupted whenever the protective enclosure is opened.
72
jadomatis 20.5 73 [[**Example: dual shutter circuits at X1.7-X1.10.**>>image:1788848686109-891.png]]
jadomatis 19.2 74
75
76 Shutter acknowledgement is provided at X1.11/X1.12. A closed and validated shutter circuit enables the laser system's active mode. The source states that laser-energy emission is possible only in active mode; a closed circuit is permission, not a marking command.
77
jadomatis 20.5 78 [[**Example: shutter acknowledgement at X1.11/X1.12.**>>image:1788848686110-868.png]]
jadomatis 19.2 79
jadomatis 20.6 80 (% class="box errormessage" %)
81 (((
jadomatis 19.2 82 **Integration requirement: **The protective enclosure, access monitoring, shutter channels, acknowledgement logic, emergency stop, and emission warning must operate as one validated safety concept. Never use the X1 examples as a stand-alone circuit design.
jadomatis 20.6 83 )))
jadomatis 19.2 84
85
86 = X1 External Inputs =
87
88 The manual states that the X1 inputs are switched using the internal 24 V auxiliary supply at X1.13. Its example closes an external contact between X1.13 and X1.14 to issue External START. X1.15 is External STOP; X1.21 and X1.22 are Inputs 4 and 5.
89
jadomatis 20.5 90 [[**Example: external input switched from X1.13 to X1.14.**>>image:1788848686111-492.png]]
jadomatis 19.2 91
92
93 = X1 External Outputs =
94
95 The source states that an active output supplies 24 V and is used with output ground at X1.25. The maximum output current is 250 mA. Status outputs are X1.16-X1.20; assignable Outputs 4 and 5 are X1.23/X1.24.
96
jadomatis 20.5 97 [[**External-output example. Confirm the selected output and load connection against the delivered electrical drawing.**>>image:1788848686112-729.png]]
jadomatis 19.2 98
jadomatis 20.6 99 (% class="box warningmessage" %)
100 (((
jadomatis 19.2 101 **Diagram limitation: **The source output figure labels X1.13, X1.14, X1.23, X1.24, and X1.25 but does not show a complete external-load connection for every output. Do not infer missing wiring from the illustration. Verify polarity, output selection, load type, current, suppression, and common reference before connection.
jadomatis 20.6 102 )))
jadomatis 20.7 103
jadomatis 20.8 104
105 = X2 Axes Interface - 25-pin Sub-D Plug =
106
107 X2 provides direction and step outputs for X, Y, Z, and R axes, zero signals, GND, and a documented +5 V supply. The image below reproduces the complete English pin table from the manual translation.
108
109 (% class="table-condensed table-striped" style="width:492px" %)
110 |=(% style="width: 108px;" %)Pin|=(% style="width: 174px;" %)Direction|=(% style="width: 207px;" %)Description
111 |(% style="width:108px" %)1|(% style="width:174px" %)Output|(% style="width:207px" %)Direction X
112 |(% style="width:108px" %)2|(% style="width:174px" %)Output|(% style="width:207px" %)Step X
113 |(% style="width:108px" %)3|(% style="width:174px" %)Output|(% style="width:207px" %)Direction Y
114 |(% style="width:108px" %)4|(% style="width:174px" %)Output|(% style="width:207px" %)Step Y
115 |(% style="width:108px" %)5|(% style="width:174px" %)Output|(% style="width:207px" %)Direction Z
116 |(% style="width:108px" %)6|(% style="width:174px" %)Output|(% style="width:207px" %)Step Z
117 |(% style="width:108px" %)7|(% style="width:174px" %)Output|(% style="width:207px" %)Direction R
118 |(% style="width:108px" %)8|(% style="width:174px" %)Output|(% style="width:207px" %)Step R
119 |(% style="width:108px" %)9|(% style="width:174px" %)Output|(% style="width:207px" %)Zero X
120 |(% style="width:108px" %)10|(% style="width:174px" %)-|(% style="width:207px" %)Not connected
121 |(% style="width:108px" %)11|(% style="width:174px" %)Input|(% style="width:207px" %)Zero Y
122 |(% style="width:108px" %)12|(% style="width:174px" %)-|(% style="width:207px" %)Not connected
123 |(% style="width:108px" %)13|(% style="width:174px" %)Input|(% style="width:207px" %)Zero Z
124 |(% style="width:108px" %)14|(% style="width:174px" %)-|(% style="width:207px" %)Not connected
125 |(% style="width:108px" %)15|(% style="width:174px" %)Input|(% style="width:207px" %)Zero R
126 |(% style="width:108px" %)16|(% style="width:174px" %)-|(% style="width:207px" %)Not connected
127 |(% style="width:108px" %)17|(% style="width:174px" %)Output|(% style="width:207px" %)GND
128 |(% style="width:108px" %)18|(% style="width:174px" %)-|(% style="width:207px" %)Not connected
129 |(% style="width:108px" %)19|(% style="width:174px" %)Output|(% style="width:207px" %)+5V supply
130 |(% style="width:108px" %)20|(% style="width:174px" %)-|(% style="width:207px" %)Not connected
131 |(% style="width:108px" %)21|(% style="width:174px" %)-|(% style="width:207px" %)Not connected
132 |(% style="width:108px" %)22|(% style="width:174px" %)-|(% style="width:207px" %)Not connected
133 |(% style="width:108px" %)23|(% style="width:174px" %)-|(% style="width:207px" %)Not connected
134 |(% style="width:108px" %)24|(% style="width:174px" %)-|(% style="width:207px" %)Not connected
135 |(% style="width:108px" %)25|(% style="width:174px" %)-|(% style="width:207px" %)Not connected
136
jadomatis 20.9 137
138
139 = X2 Functional Grouping =
140
141 (% class="table-condensed table-striped" style="width:1125px" %)
142 |**Axis / function**|(% style="width:391px" %)**Pin(s)**|(% style="width:481px" %)**Direction stated in manual**
143 |X axis|(% style="width:391px" %)1 Direction; 2 Step; 9 Zero|(% style="width:481px" %)Outputs on all three pins, as stated
144 |Y axis|(% style="width:391px" %)3 Direction; 4 Step; 11 Zero|(% style="width:481px" %)Direction/Step outputs; Zero input
145 |Z axis|(% style="width:391px" %)5 Direction; 6 Step; 13 Zero|(% style="width:481px" %)Direction/Step outputs; Zero input
146 |R axis|(% style="width:391px" %)7 Direction; 8 Step; 15 Zero|(% style="width:481px" %)Direction/Step outputs; Zero input
147 |Reference|(% style="width:391px" %)17 GND; 19 +5 V|(% style="width:481px" %)Outputs, as stated
148 |Not connected|(% style="width:391px" %)10, 12, 14, 16, 18, 20-25|(% style="width:481px" %)NC
149
150
151
152 = Integration and Commissioning Checks =
153
154 * (((
155 Confirm X1 is a 25-pin Sub-D socket and X2 is a 25-pin Sub-D plug before preparing mating connectors.
156 )))
157 * Keep safety functions, production commands, status monitoring, axis signals, and workstation connections identified separately in the electrical documentation.
158 * Verify conductor identification, shielding, routing, protective bonding, connector retention, strain relief, and separation from interference sources for the delivered installation.
jadomatis 20.10 159 * Validate both emergency-stop channels, both shutter channels, acknowledgement behavior, guard opening, status outputs, and prevention of unexpected restart before laser operation is released.
jadomatis 20.9 160 * Confirm the External START/STOP logic and LASER READY/BUSY/END sequence against the host control specification without bypassing any safety permission.
jadomatis 20.10 161 * For every installed axis, verify direction, step scaling, travel limits, zero/reference behavior, and safe motion before placing a workpiece in the marking area.
jadomatis 20.9 162 * Document measured results and obtain the required approval for the complete integrated machine, not only the Auto-Light rack.
163
jadomatis 20.10 164 (% class="box infomessage" %)
165 (((
166 **Troubleshooting boundary: **Operators may record external status and host messages. Pin-level measurement, connector removal, rewiring, safety-module work, and axis electrical testing require isolation and personnel authorized for the delivered integration. Use the Auto-Light Troubleshooting article for symptom-based diagnosis.
167 )))